Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

...

  • Communication protocol: VONSCH VQfrem 400.
  • The station address is a 16-bit number (1-32767). It can be entered decimally (e.g., 1 or 1234) or hexadecimally using a hash (e.g. #0001 or #4D2).
    Address 32768 (#8000) serves as a broadcast for commanding - all devices receive it, but none respond to it.

...

Table 2 - Status register of a converter

BitMeaningLogical 0Logical 1
0Motor voltagedisconnectedconnected

1

Converter is ready for START via serial linknot readyready
2Converter is reset via serial linkOFFON
3Reverse - required frequency or position is negative OFFON
4Motor readynot readyready
5Active setSET1SET2
6Converter is resetOFFON
7Terminal switch 2not readyready
8Faultdidn’t occuroccurred
9Warningdidn’t occuroccurred
10Start / Stopin stopin start
11End of trial operationOFFON
12Critical warning didn’t occuroccurred
13Frequency change at the output of ramp generatornot finishedfinished
14Position calibration commandnot receivedreceived
15Password authorizationnot validvalid



Table 3 - Quantities available for reading according to the documentation

AddressDescriptionMeaning
#0001Software version609h for ver. 6.09, (402h for ver. 4.02, 304h for ver. 3.04)

#0004

Voltage range190h for 400V, 191h for 400 ...M, 2b2h for 690V
#0025Freq. INV - the frequency of voltage on converter’s output (stator frequency) +/- XXX,XX Hz
#0026Revolves - output revolutions of the motor+/- XXXX rev/min
#0027Revol/i - evolutions behind gear/transmission+/- XXXX,X rev/min
#0028Freq.RT - rotor frequency (evaluated from speed encoder – IRC)+/- XX,XX Hz
#0029Freq.RF - required converter frequency+/- XX,XX Hz
#002A

MT Curr. - effective current value into the motor

XXX,X A
#002BR.torque - required mechanical motor torque +/- XXX,X Nm
#002CTorque - mechanical motor torque +/- XXX,X Nm
#002DMag. flux - rotor magnetic fluxX,XXX Wb
#002EVolt. MT - momentary motor supply voltage (100.0% responds to 400 V)XXX,X %
#002FVolt. DC - real voltage of converter’s unidirectional DC busXXX V
#0030Inp.pow. - momentary input power into the motorXXX,X kW
#0031

MT power - motor power

XXX,X kW
#0032kW hours - motor energy consumption in kWhXXXX kWh
#0033MW hours - motor energy consumption in MWhXXXX MWh
#0034Teplota chladiča meničaXX,X °C
#0035Temp.INV. - air temperature in the converterXX,X °C
#0036PR ref. - required value of process regulatorXX,X %
#0037PR real - feedback of process regulator (real value)XX,X %
#0038Inp. AIN1 - the value of analogue input AIN1 in % rangeXX,X %
#0039Inp. AIN2 - the value of analogue input AIN2 in % rangeXX,X %
#003AHodnota analógového vstupu 3 v % rozsahuXX,X %
#003B

BIN 1-6 - status of binary inputs BIN 1 - BIN 6 (bits 0-5 from the received value - bit numbering is from 0 to 15). 

0=input is open
1=input is closed
#003C

RELAY 1-2,3 - the status of relay inputs RELAY 1 - RELAY 4  (bits 8-10 from the received value - bit numbering is from 0 to 15). 

0=relay is open
1=relay is closed
#003DHours INV - converter operating time counterXXXX h
#003EHours MT - motor operating time counterXXXX h
#003FPos.ref. - required position in a case of „position“ variable+/- XXXX,X cm
#0040Position - real position+/- XXXX,X cm
#0041Pos. TSW2 - the trajectory for running down when Terminal switch TSW2 is on+/- XXXX cm
#0042Deviation from zero position when calibrating the ARC position sensorXXXX d
#0043cos(fi ) - momentary value of motor power factor+/- X,XX
#0044See Warnings register 2-
#0045See Warnings register 1-
#0046

See See the Faults register

-
#0048Overload - a momentary value of overloadXXX.X %
#0049Service SL - service displayed variable Slave+/- XXXX d
#004aService MS - service displayed variable Master

+/- XXXX d

All values are transmitted as 16-bit numbers. The KOM process interprets them as signed or positive by address
(signed are #0025-#0027#0029,  #002B#002B,  #002C#002C, #003F-#0041,  #0043#0043,  #0049#0049-#004a).

If the number is fractional, the corresponding linear conversion must be entered in the I/O tag configuration in the Conversion tab (e.g., coefficient A=0.1 for #0030, A=0.01 for #0028).

...