| Parameter | Description | Unit / size | Default value | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Activates detailed debug information about sending and receiving values. | YES/NO | NO | ||||||
| The version of the MQTT protocol that will be used to connect to the MQTT server. It is possible to use the older MQTT 3.1.1 standard (October 2014) or the newer MQTT 5.0 standard (March 2019). MQTT brokers usually support both standards, the older standard is simpler and more economical. | MQTT 3.1.1 MQTT 5.0 | MQTT 3.1.1 | ||||||
| User name used in a CONNECT message to connect to the MQTT server. | - | |||||||
| Password used in a CONNECT message to connect to the MQTT server. | - | |||||||
| The name of one topic or a multiple-topic filter sent within the SUBSCRIBE message. Using the filter the MQTT client specifies topics, within which it wants to receive messages. Note: topics are hierarchically sorted, a slash (/) is used as the separator, a plus (+) is used as a one-level mask, a hash (#) character is used as a mask for multiple levels. Examples of filter: a/b , level1/+ , # , +/+/+/up Note: the change of the Topic Filter parameter will be reflected after restarting the communication - e.g. due to the breakdown of the TCP connection, as long as all stations on the line are switched off (StOff) and switched on again, or after a restart of the KOM process. In the first two cases, the message UNSUBSCRIBE is sent to the original Topic Filter and then SUBSCRIBE to the new Topic Filter (this can be important in so-called persistent sessions when the Client ID parameter is specified and the MQTT server remembers the state of the client even after the TCP connection is broken). Note: for Payload Type = Sparkplug Host, the filter spBv1.0/# is sufficient to receive all Sparkplug messages. Note: for Payload Type = Sparkplug Edge Node, a SUBSCRIBE message is automatically sent to all NCMD/DCMD topics derived from the addresses of Edge Node/Device stations configured on the link. Example:
Note: Payload Type = Sparkplug Edge Node, a SUBSCRIBE message is automatically sent to the topic spBv1.0/STATE/<primaryHostApplication> if the Sparkplug Host ID parameter is specified (<primaryHostApplication> is the value of this parameter), so that the D2000 KOM process is informed about the connection/disconnection of the Primary Host Application. If a STATE message about the Primary Host Application disconnection is received (STATE message with online=false) and multiple IP addresses are specified in the line configuration, the D2000 KOM process disconnects from the current MQTT server and tries other MQTT servers until it finds one to which the Primary Host Application is connected (STATE message with online=true). | - | # | ||||||
| The desired maximum level of validation (QoS) sent within the SUBSCRIBE message. The MQTT server can then send PUBLISH messages with such or lower levels of confirmation (but not higher). PUBLISH messages sent by the MQTT server will be confirmed by the D2000 KOM process according to the level of confirmation specified in them. The higher the level of confirmation, the more messages between the client and the server are exchanged (1 at QoS_0, 2 at QoS_1, and 4 at QoS_2). | QoS_0 QoS_1 QoS_2 | QoS_1 | ||||||
| Unique client identifier (Client Identifier) sent within the CONNECT message. The tested MQTT server (thethings.network) returned an error if the Client ID was blank and Clean Session Flag=NO. Note: Some MQTT brokers (PIXII.COM, Eclipse Mosquitto) identified clients only by Client ID. In practice, this meant that two different D2000 systems that connected to the same broker were considered as one client, and the broker closed an existing connection that it considered old when a new connection was established, or it did not allow a new connection to be created and returned the error Connection Refused, identifier rejected (2). | - | D2000kom | ||||||
| Parameter Clean Session Flag of the CONNECT message. The NO value means that the server uses the current session state (connection) - e. g. after the collapse and recovery of the TCP connection. This means that all unconfirmed PUBLISH messages with QoS_1 and QoS_2 are resent (optionally also QoS_0, depending on the implementation). | YES/NO | NO | ||||||
| Level of confirmation (QoS) used to send PUBLISH messages through the D2000 KOM process. Sending the PUBLISH message is the outcome of writing into the output tag with the OUT_VALUE address. The higher the confirmation level, the more messages between the client and server are exchanged (1 for QoS_0, 2 for QoS_1, and 4 for QoS_2). | QoS_0 QoS_1 QoS_2 | QoS_0 | ||||||
| Setting the Retain flag used when sending PUBLISH messages by the D2000 KOM process. Activating the Retain flag causes the last message sent by the D2000 KOM process to be available on the MQTT server to other clients immediately after they are connected, as well as after the D2000 KOM process is disconnected. | YES/NO | NO | ||||||
| Parameter Keep Alive sent as part of a CONNECT message. The recommended Keep Alive value is several minutes. The D2000 KOM process sends PING requests according to the settings of the Keep Alive and Ping Interval parameters (whichever interval expires first). | 0-65535 sec | 0 | ||||||
| If the MQTT server did not send any message during the specified time interval, the D2000 KOM process sends a PING request and waits for a PING response (until time Reply Timeout). A value of 0 turns off sending the PING request messages. The parameter allows detection of TCP connection failure. | 0-3600 sec | 60 | ||||||
| The setting of message parsing:
| Text only JSON Sparkplug Host Sparkplug Edge Node | Text only | ||||||
| If Payload Type=JSON, the name of the field with a timestamp. If the field name is not specified or the field is not found, the current time is assigned to the values. For more information on the field name format, see I/O tags with addresses JA=json_address. | - | - | ||||||
| Mask for parsing a value in the field with a timestamp. Special masks are:
Note: Whether the time is interpreted as local or UTC with a configured offset depends on the time station parameters settings. | - | yyyy-mm-dd hh:mi:ss.mss | ||||||
| Ignoring a missing timestamp - if it is not present in the JSON payload, no warning will be issued. | YES/NO | NO | ||||||
| Parameter Will Flag of a CONNECT message. A value of Yes means that the server will send a Last Will message to interested parties if the connection to the D2000 KOM process is lost. Note: If Payload Type = Sparkplug Host and the Sparkplug Host ID parameter is not empty, this parameter is ignored and Last Will will be sent (see the description of the Sparkplug Host ID parameter). Note: If Payload Type = Sparkplug Edge Node, this parameter is ignored and Last Will will be sent (see the description of the Sparkplug Host ID parameter). | YES/NO | NO | ||||||
| The acknowledgment level (QoS) used when sending a Last Will message in the event of a loss of connection to the D2000 KOM process. Note: If Payload Type = Sparkplug Host and the Sparkplug Host ID parameter is not empty, this parameter is ignored, and QoS_1 level will be set (see the description of the Sparkplug Host ID parameter). Note: If Payload Type = Sparkplug Edge Node, this parameter is ignored, and QoS_1 level will be set (see the description of the Sparkplug Host ID parameter). | QoS_0 QoS_1 QoS_2 | QoS_0 | ||||||
| The setting of the Retain flag used when sending a Last Will message if the connection to the D2000 KOM process is lost. Note: If Payload Type = Sparkplug Host and the Sparkplug Host ID parameter is not empty, this parameter is ignored and Retain is set to YES (see the description of the Sparkplug Host ID parameter). Note: If Payload Type = Sparkplug Edge Node, this parameter is ignored and Retain is set to NO (see the description of the Sparkplug Host ID parameter). | YES/NO | NO | ||||||
| The topic used to send the Last Will message if the connection to the D2000 KOM process is lost. Note: If Payload Type = Sparkplug Host and the Sparkplug Host ID parameter is not empty, this parameter is ignored (see the description of the Sparkplug Host ID parameter). Note: If Payload Type = Sparkplug Edge Node, this parameter is ignored, and Topic is set according to the Sparkplug standard (see the description of the Sparkplug Host ID parameter). | - | |||||||
| Contents of the Last Will report if the connection to the D2000 KOM process is lost. Note: If Payload Type = Sparkplug Host and the Sparkplug Host ID parameter is not empty, this parameter is ignored (see the description of the Sparkplug Host ID parameter). Note: If Payload Type = Sparkplug Edge Node, this parameter is ignored, and Last Will is set according to the Sparkplug standard (see the description of the Sparkplug Host ID parameter). | - | |||||||
| If the MQTT server does not respond to the SUBSCRIBE, UNSUBSCRIBE, and PING requests within the required time or the D2000 KOM process fails to read a complete message (and only part of it is read), the D2000 KOM process declares an error, closes the connection, and opens it again. Value 0 turns off the timeout. | sec | 20 | ||||||
| A timeout of a single reading from a TCP connection. D2000 KOM repeats reading of spontaneous data Max. Wait Retry times and if no data is read, the reading is timeouted and finished (and may be followed by a further reading or writing). By lowering Wait Timeout and Max. Wait Retry parameters, it is possible to achieve a faster writing response of the D2000 KOM process at the expense of a higher CPU load when the MQTT server has no data. | sec | 0.100 | ||||||
| The number of repetitions of reading from the TCP connection. See the description of the Wait Timeout parameter. | - | 3 | ||||||
| Payload field encoding. The MQTT protocol does not specify the content of the Payload field; the ISO-8859-1 standard encoding is suitable for both text and binary content, and UTF-8 is suitable if UTF-8 encoded texts are transmitted. Currently supported encodings are:
| - | ISO-8859-1 | ||||||
MQTT 5.0 Parameters | |||||||||
| Number of Topic Aliases that can be sent by the MQTT broker (parameter is sent in the CONNECT message). The value 0 (default) means that Topic Aliases are not used. The parameter is used only for MQTT Version = MQTT 5.0. Topic Aliases are numeric identifiers from the interval <1 ... Topic Alias Maximum>, which are sent by the D2000 KOM and the MQTT Broker instead of text identifiers. Note: In the CONNACK message (response to CONNECT), the MQTT broker optionally sends its value "Topic Alias Maximum", which has the meaning of the number of Topic Aliases that can be sent by the D2000 KOM process (e.g. test.mosquitto.org sends the value 10). D2000 KOM uses Topic Aliases only if the value of its configuration parameter Topic Alias Maximum is non-zero. | 0 | 0 - 65535 | ||||||
Sparkplug parameters | |||||||||
| The parameter activates listings of unknown metrics and topics that do not have their own stations, but end up at a station with the address ".*" (if there is any). The listings will be in the line log as error messages even if the debug on the line is turned off (to facilitate the addition of I/O tags). | YES/NO | NO | ||||||
| Activation of parsing of non-standard SparkPlug topics (if Payload Type = Sparkplug Host). | YES/NO | NO | ||||||
| Within the metric, it is possible to define a property called Quality of type Int32. According to the Sparkplug standard, it must be one of the values 0=BAD, 192=GOOD, 500=STALE. Any other D2000 Kom process reports as an error. The Ignore Unknown Quality parameter can be used to suppress this error message. | YES/NO | NO | ||||||
| The parameter specifies which addresses of the Dataset metric are displayed when browsing:
| - | Columns only | ||||||
| Separator of individual levels in Templates used when entering the address of the I/O tag in Sparkplug mode. | -> | |||||||
| If Payload Type = Sparkplug Host: Identifier of Host Application (D2000 is a Host Application). If Payload Type = Sparkplug Edge Node: Identifier of Primary Host Application (Identifier of the Host Application that is defined as primary - the most important - for this Edge Node). | - | - | ||||||
| If Payload Type = Sparkplug Edge Node, the parameter enables Store & Forward functionality for all stations on the line. If communication is down, values are stored in memory and sent with the is_historical flag when communication is restored. | YES/NO | NO | ||||||
| Adding a textual representation of the value type (e.g. Int32) and a timestamp to the text I/O tag with IN_SP2JS address used to convert the Sparkplug payload to JSON for optional parsing in an ESL script. | YES/NO | NO | ||||||
...