Full name | Description | Unit | Default value | ||||||
---|---|---|---|---|---|---|---|---|---|
| Defines the time interval for the server to send the information about the change of monitored items within the instance subscription by "Publish message". | mi:ss.mss | 00:05.000 | ||||||
| If the client does not send the request for data till the time defined by (LifeTime Count * Publishing Interval), the subscription expires. The value should be minimally 3 times higher than the "Requested Max KeepAlive Count". | Number | 1000 | ||||||
| If the objects of subscription are not changed, the server will send a keep-alive message after elapsing the time (Max Notifications Per Publish * Publishing Interval). The client will confirm this message when it sends a new request for data. | Number | 5 | ||||||
| The parameter defines the maximum number of notifications about the object change, which the server can send in one "Publish message". Zero indicates that the number of notifications is unlimited. | Number | 0 | ||||||
| The parameter enables/disables the publishing within the subscription. | YES/NO | YES | ||||||
| It defines a relative priority of a subscription. If the server should send more notifications, the subscription with higher priority is preferred. | 0-255 | 0 | ||||||
| This parameter enables creating an object queue with the defined length on the OPC UA server's side for each monitored item in a subscription. | Number | 0 | ||||||
| Timestamps used while reading a value:
| - | Server | ||||||
| Timestamps used to write a value:
Note: If the OPC server does not support the writing of timestamps, according to the standard it should return the Bad_WriteNotSupported (2155020288) error code. | - | None | ||||||
| StatusCode item will be used when writing. Note: According to the standard, the OPC UA Wrapper returns the Bad_WriteNotSupported (2155020288) error code if the StatusCode entry is used when writing to the OPC DA Server version 2.05a. | YES/NO | YES | ||||||
| When an item of an array is written, the entire array is read first and then written. If this parameter is set to NO, only a specific array item is written, Note: According to the standard, if the OPC server does not support writing a specific array item, it should return the Bad_WriteNotSupported (2155020288) error code. Note: If this parameter is active, the "Write only" parameter must not be set at the I/O tag which addresses an item of the array. | YES/NO | NO | ||||||
| A way of reading values:
Note: The Subscribe+Read and Read modes should only be used if there is a problem with standard communication, as they are less efficient and have a higher overhead. | Subscribe Subscribe+Read Read | Subscribe | ||||||
| Ignoring filter parameters in the I/O tag configuration (Sampling type, DeadBand type, Trigger type). | YES/NO | NO | ||||||
| The maximum number of consecutive unconfirmed Publish requests (to which OPC UA server does not reply with a Publish Message), after which the connection will be closed. A value of 0 causes the connection to not be closed. Note: This parameter can be used to speed up the detection of a broken connection to the OPC UA server. | - | 0 |
...