Defined Functional Constraints according to ISO/IEC IEC 61850-8-1:
FC Name | Description |
---|---|
MX | Measurands (analog values) |
ST | Status information |
CO | Control service parameters |
CF | Configuration |
DC | Description |
SP | Setting (outside setting group) |
SG | Setting group |
RP | Unbuffered report control blocks |
LG | Log control blocks |
BR | Buffered report control blocks |
GO | GOOSE control blocks |
GS | GSSE control blocks |
SV | Substituted values |
SE | Setting group editing |
MS | Multicast Sampled Values control block |
US | Unicast Sampled Values control block |
EX | Name space for model extension |
SR | Service tracking |
OR | Operate received |
BL | Blocking |
Names of DataObject Attributes and SubDataObject Attributes are defined in ISO/IEC IEC 61850-7-3 and the following table contains only the most common ones:
...
For the Structure object type: it is possible to specify the index where IEC 61850 Quality is located. The format of the Quality Index is the same as a complex address.
IEC 61850 Quality is of Bitstring type with a length of 2 bytes. 13 quality bits are defined as follows (the standard numbers the bits so that the highest bit is 0 and the lowest is 15):
Bit(s) | Note | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
0-1 | Validity:
| |||||||||||||||
2 | Overflow | |||||||||||||||
3 | OutofRange | |||||||||||||||
4 | BadReference | |||||||||||||||
5 | Oscillatory | |||||||||||||||
6 | Failure | |||||||||||||||
7 | OldData | |||||||||||||||
8 | Inconsistent | |||||||||||||||
9 | Inaccurate | |||||||||||||||
10 | Source ( 0-Process, 1-Substituted) | |||||||||||||||
11 | Test | |||||||||||||||
12 | OperatorBlocked | |||||||||||||||
13-15 | unused bits |
...