Date: Thu, 28 Mar 2024 22:43:04 +0100 (CET) Message-ID: <136919748.111288.1711662184279@srvdoc.doc.ipesoft.com> Subject: Exported From Confluence MIME-Version: 1.0 Content-Type: multipart/related; boundary="----=_Part_111287_1494364731.1711662184279" ------=_Part_111287_1494364731.1711662184279 Content-Type: text/html; charset=UTF-8 Content-Transfer-Encoding: quoted-printable Content-Location: file:///C:/exported.html
Supported device types and =
versions
Co=
mmunication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
The protocol allows reading and writing data from control PLC automats o= f Siemens Simatic of the S5 and S7 series. PLC Simatic must be equipped wit= h the following serial communication point-to-point modules:
The protocol RK512 is a transport superstructure of protocol 3964(R). It allows unive= rsal reading and writing values of PLC Simatic objects - minimal interventi= on into the PLC application software (using the STEPS5/7 programming langua= ge).
The 3964 protocol, which is the line layer of the RK512 protocol, has tw= o variants - 3964 a 3964R. The 3964R allows extra data security using the B= CC checksum.
The Communication station configuration dialog box - tab Table 1 Possible I/O tag value types: Ai, Ao, Ci, Co, Di, Do.=
p>
I/O tag address is a character string as follows: Table 2 Table 2 contains the address format used in SIMATIC S5, i.e. use of word=
offset in DB and DX elements. Therefore you can use addresses in the S7 fo=
rmat according to table 3 for DB and DX elements: Table 3 Explanatory text: Note 1: - Related pages:
Parameters defined in the input field have an effect on some optional prot=
ocol parameters. The following station protocol parameters can be defined:<=
/p>
Parameter
Meaning
Unit / size
Default value
Maximum co=
unt of request retries. If no response returns after a request had been sen=
t, the station's status will change to a communication error.
-
2
Timeout be=
fore resending a request if no response has been received.
ms
100 ms
The delay =
after sending the request and before reading the response.
ms
100 ms
The delay =
between the response readings.
ms
50 ms
The maximu=
m number of retries of the response reading.
-
40
Enable the 3964 link protocol, i.e. version with=
no transmission security. By default, the 3964R protocol is used, which im=
plements the BCC checksum.
YES/NO
NO
CPU identification (1 up to 4), not used by defa=
ult (value =3D 0).
0,1,2,3,4
0
I/O t=
ag configuration
Data
Format
Description
Access
I/O tag type
Data block/Extended data block elements
D{B|X}mD{L|R|W|D}n[x]
m =3D "data block" number
n =3D word offset in the data block
x =3D suffix KF,KG (as necessary - see Note 1)R/W
Ai, Ao, Ci, Co
Data block bits
D{B|X}mDn.k
m =3D "data block" number
n =3D word offset in the data block
k =3D bit position [0..15]R/W
Di, Do
Memory elements
F{Y|W|D}n[x] or M{B|W|D}n[x]
n =3D byte offset in "memory area"
x =3D suffix KF, KG (as necessary - see Note 1)R
Ai, Ci
Memory bits
Fn.k or Mn.k
n =3D byte offset in "memory area"
k =3D bit position [0..7]R
Di
Input elements
I{B|W|D}n[x] or E{B|W|D}n[x]
n =3D byte offset in "input area"
x =3D suffix KF, KG (as necessary - see Note 1)R
Ai, Ci
Input bits
In.k or En.k
n =3D byte offset in "input area"
k =3D bit position [0..7]R
Di
Output elements
Q{B|W|D}n[x] or A{B|W|D}n[x]
n =3D byte offset in "output area"
x =3D suffix KF, KG (as necessary - see Note 1)R
Ai, Ci
Output bits
Qn.k or An.k
n =3D byte offset v "output area"
k =3D bit position [0..7]R
Di
Data
Format
Description
Access
I/O tag type
Data block/Extended data block elements
D{B|X}m.DB{B|W|D}n[x]
m =3D "data block" number
n =3D byte offset in the data block
x =3D suffix KF, KG (as necessary - see Note 1)R/W
Ai, Ao, Ci, Co
Data block bits
D{B|X}m.DBXn.k
m =3D "data block" number
n =3D byte offset in the data block
k =3D bit position [0..7]R/W
Di, Do
The suffix is optional as follows:=
p>