Date: Fri, 29 Mar 2024 09:57:59 +0100 (CET) Message-ID: <1579208585.111606.1711702679455@srvdoc.doc.ipesoft.com> Subject: Exported From Confluence MIME-Version: 1.0 Content-Type: multipart/related; boundary="----=_Part_111605_846564742.1711702679455" ------=_Part_111605_846564742.1711702679455 Content-Type: text/html; charset=UTF-8 Content-Transfer-Encoding: quoted-printable Content-Location: file:///C:/exported.html
Support=
ed device types and versions
Communication line configuration
Station configuration=
I/O tag con=
figuration
Docu=
ment revisions
The protocol supports reading data from electrometers (active and reacti=
ve energies) that were collected by ABB Microscada system and published via=
files.
The files are expected to have a name in a format coding both the date and=
the time Dyyyymmddhhmi.CSV, e.g. D201706301247.CSV.
The files are read with the time parameters (period, delay) configured on =
the station's Time parameters tab.
The protocol only supports data readout.
Dialog window station configuration - tab "Protocol parameters".<= br> They influence some optional protocol parameters. The following station pr= otocol parameters can be entered:
Parameter | Description | Unit | Default Value |
---|---|---|---|
Delay After Processing File
|
Delay after processing of a file. The parameter = can be useful if the communication has been offline for a longer time, i.e.= a larger number of files are accumulated and their fast processing could f= lood the system. | s | 0 |
Supported value types of I/O tags: Ai.
I/O tag address is an integer 16-bit number (1-65535) specified as a dec=
imal number or as a hexadecimal number with a hash at the beginning (e.g. #=
0A).
It defines an electrometer number, which is specified on every line of a d=
ata file.
This is an example of the first 15 rows of a specific file (I/O tag addres=
ses would be 1-15):
E001;0 E002;6504 E003;0 E004;0 E006;3620 E007;1160 E008;196 E009;884 E010;152 E011;400 E012;140 E013;3588 E014;0 E015;0