SNMP protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tags configuration
Messages of Trap type receiving and processing
Browsing and reading the tree of values from the script
Literature
Changes and modifications
Document revisions

Supported device types and versions


SNMP protocol (Simple Network Management Protocol) is used for monitoring and administration of network components. It allows the detection of the network devices' status and the changing of their settings. In an application, it is possible to monitor the functionality of e.g., routers, switches, computers, etc.

To create a station equipped with the SNMP protocol, it is necessary to have a UDP line (of TCP/IP-UDP type). It is worth mentioning here that a TCP/IP-UDP line in the perception of the D2000 system is actually a UDP socket, which is a logical device to support communication of individual stations. It is not possible to use stations with a different protocol on a line where stations with the SNMP protocol exist!

Communication line configuration


  • Communication line category: TCP/IP-UDP.
  • UDP parameters:
    • Host: There are three ways:
      1. The IP address of the particular network interface – datagrams will be transmitted and received only via this interface.
        Example:  192.168.1.10
      2. The symbolic name of a particular network interface.
        Example:  D2SRV_PRIMARY
      3. ALL -the configured UDP port is opened on all available network interfaces. An optimal network interface should be used for communication based on routing tables. The reception of messages will be performed on all network interfaces.
    • Port: UDP port number (0 through 65535) from which the D2000 KOM process sends requests and receives responses. If the value is 0, the port number is assigned automatically by the OS.
      Note: Ports 161 and 162 are the standard UDP ports used in SNMP, but they are often reserved for SNMP agents - that is why it is recommended to choose different ports. Problems can occur with value 0 (zero) if the network uses firewalls and other security measures. Then, a specific port needs to be configured on the firewalls so that the packets from this port are passed through the firewalls.

Note:
If SNMP protocol needs to run in a redundant system, where two instances of the D2000 KOM process are running concurrently on two different computers and the IP address cannot be positively determined in the line configuration, it is appropriate to choose „ALL“ configuration option or to name the network addresses identically as e.g. SNMP_LAN and assign them a correct IP address in the hosts file of each computer. See example:

on Computer 1:192.168.0.1SNMP_LAN
on Computer 2:192.168.0.11SNMP_LAN


Protocol parameters on the line

The following parameters of the protocol can be set on the line:

KeywordFull nameDescriptionUnitDefault value
TRACE
Trace Level
Trace level = 0- no debugging information output, the same as turning it off in the Line parameters
Trace level = 1- only information on receiving and sending UDP packets and IP addresses
Trace level = 2- adds information on request preparation
Trace level = 3- adds packet's HEX dump
Trace level = 4- the same as the value of 3
Trace level = 5- adds:
  • detailed analysis of packet structure in ASN.1 encoding
  • order of data in the packet
  • detailed information
Trace level = 9999- adds information on the preparation and decision making of packet distribution, and on searching


The values 5 and 9999 are intended for debugging, and their permanent use is not recommended. In case that the information is needed from a monitored station(s) only, the setting of the Trace level can be performed for a particular station in its configuration dialog box.

The value of 1 is recommended for ordinary operation.

-1
TE
Trap EnableEnables to receive the messages of the Trap type.BooleanFalse
TTI
Trap IP AddressThe IP address for receiving the Trap messages.-ANY
TTP
Trap PortUDP port for receiving the Trap messages.-162

Communication station configuration


  • Communication protocol: SNMP Manager.
  • Station's address: it is defined in the format IP_address1[:port1], IP_address2[:port2].

IP_address may be set in decimal dotted notation (e.g. 192.168.0.1) or as a name (e.g. SrvMoxa1), which assumes address translation by means of DNS or a hosts file. Address1 and Address2 concern the existence of primary and backup lines/routes. Address 2 is usable, for example, for a server containing two network interface cards, which is connected to two different network segments available via two different network paths.

Port is a number in the range 1..65535 on which an SNMP agent expects communication to take place. As the default (if not configured, or set to 0) port, the standard port 161 will be used.

Note:

  • If the line has only a primary IP address configured (numerical or symbolic), UDP packets are sent from this address to both IP addresses of the station. One numerical primary IP address of the line + two IP addresses of the station are valid for a network topology where the local network is non-redundant, but the remote network (where the station is located) is accessible via two redundant communication paths.
  • If the line has both IP addresses configured, UDP packets to IP_address1 leave from the primary IP address of the line, and UDP packets to IP_address2 leave from the backup IP address of the line.
    The situation when, e.g., IP_address1 is not configured conforms to the topology when the station is connected to a backup communication path only.


Protocol
The employed version of the SNMP protocol – one of the options can be selected:

  • SNMP_V1 – the oldest version – does not support any secured access to the SNMP agent. It only distinguishes the objects that are freely accessible (public) and those belonging to a restricted group (private).
  • SNMP_V2 – a version that supports authentication to access individual data types - an agent might (not) provide a particular set of data for an anonymous user (a manager,...) and different data for a user whose identity has been verified by entering a correct name and password.
  • SNMP_V2C – the same as SNMP_V2 – the D2000 system does not distinguish these variants.
  • SNMP_V3 – so far the latest protocol version – besides functions provided by SNMP_V2C, supports functions for authentication and encryption. It requires entering the name of an authentication server and authentication keys to authenticate prior to communication with an agent, and keys for encrypting communication.

SNMP_V2, SNMP_V2C, and SNMP_V3 are not supported yet. Neither writing into the SNMP agent nor reading MIB branches as a table (structured I/O tags or directly entered structure entries) is supported.


Station protocol parameters

The following station protocol parameters can be set:

Table no. 2

KeywordFull nameDescriptionUnitDefault value
WT
Wait TimeoutThe timeout period for the response to the read request.ms
RC
Retry CountA number of times, the read requests are resent before the reading is considered unsuccessful, and another I/O tag will be read.-
EC
Max Error CountMaximum count of unsuccessful read requests, until the station changes its value to the StCOMERR state. A successful value delivery nullifies all counters and puts the station back into StON state.-

AR

Address Root

A prefix that will be added to the addresses of all I/O tags on the station. Using the prefix, it is possible to shorten the addresses written in the I/O tag configurations.
Example: If Address Root=1.2.3.4.5.6.7.8 and the address of the I/O tag is .9.10, then the resulting address is 1.2.3.4.5.6.7.8.9.10.

-
TL
Trace LevelThe same meaning as parameter Trace Level on a line, but this setting is valid for the particular station. However, the higher value of a line parameter Trace level takes precedence.
Note: Debugging of incoming packets is influenced by the line parameter Trace Level because, at the time of reception, it is still unknown which station the packet belongs to.
-

I/O tags configuration



Address1: Address of I/O tag. The address specifies the OID (Object identifier) of an object. It is displayed in a numerical format, e.g., 1.3.6.1.2.1.1.1.0. The address can also start with a dot, which is ignored, unless the Address Root parameter is set (e.g., .1.3.6.1.2.1.1.1.0),

An I/O tag with such an address will all be read via a network path, which is currently operational (a primary or a backup line is determined according to the result of a reply to a previous request, or possibly can be switched automatically).

If it would be necessary to have information on whether the primary or backup IP address of the device is available, it is possible to use the so-called forced addressing by selecting the option Only Primary, respectively Only secondary. This will ensure that the I/O tag value will be acquired only from the primary, respectively, secondary station address. The Both option is the standard option, where the values of the I/O tags are obtained continuously from both addresses of the station (if they are configured). The Passive option means that the value of the I/O tag is not read directly, but is obtained indirectly as a copy of the value of another I/O tag with the same address, but in the active mode, e.g., Only primary.

If the object with a specified OID address does not exist, the SNMP agent returns an error code with a different OID address (because the object with the required OID does not exist), and therefore, the communication will be denoted as unsuccessful. The I/O tag passes to the „Unknown value“ state. If it is necessary to indicate the line status by value change and not by the validity of the object's value, the object of DI type can be created, an integer value (e.g. UpTime) can be asked for and an automatic number to boolean conversion can be utilized, where 0 is converted to false and the other values to True. The I/O tag can then be configured to use a default value and to set the default to False. Then the object may acquire only the values True or False, depending on the object's availability in the SNMP agent.

The I/O tag with an address starting with %IGNORE will be ignored.


Request: The Default value Get causes the values to be read by a Get SNMP request.
Some devices have problems providing values by the Get request if the object is an item of an array. Then, you must configure the type of request GetNext, and the address should be the OID of the previous object (to find the address, use the Java application MIB Browser (http://tl1.ireasoning.com/mibbrowser.shtml) that reads the whole tree of values and detects the OID address of the previous object).


Time delay: Offers a possibility to set a delay period for particular I/O tags, to optimize the network's load. This time is added to the current time after a successful reading of the I/O tag's value, and the next request will be processed as soon as the current time is greater than or equal to the time calculated in this way.
If the object's value is unknown, the object will be included in communication in the next periodic request (according to the time parameters of the station), regardless of the delay time.
The time delay parameter does not influence the processing of TRAP messages if the TRAP has the same address as the /O tag.

After receiving the value from the SNMP agent, the conversion will be done according to the real type of value in the SNMP protocol and the required type in the D2000 system. If it is not possible to carry out the conversion, the value will be invalid, and a report about the wrong conversion will be logged into a trace file.

ASN1 value type: Specifies the value type in the SNMP agent's response. It also determines applicable conversions. The value type can be detected in the MIB database (note: MIB database browser is not a part of the solution). One of the freely available browsers can be used, and the desired data format can be set based on the obtained information. It is recommended to use the MIB Browser Java application  (http://tl1.ireasoning.com/mibbrowser.shtml).

Possible value types:

Integerinput value - expected as a signed integer number (up to 64-bit *)
Unsignedinput value - expected as an unsigned integer number (up to 64-bit *)
Floatinput value - expected as a floating-point number (float, a long float)
Textinput value - text string
IP addressthe input sequence of bytes interpreted as a sequence of numbers separated by a dot – the sequence is converted to text
Hex textthe input sequence of bytes is interpreted as a sequence of hexadecimal numbers separated by a colon – the sequence is converted to text

The value types IP address and Hex text can be applied to an arbitrary input data type, which will be further handled as a sequence of bytes. E.g., the input value of text type with value "test@ipesoft.sk" can be interpreted in the following ways:

Text: "test@ipesoft.sk"
IP address: „112.101.114.105.99.104.64.105.112.101.115.111.102.116.46.115.107“7“
Hex text: „70:65:72:69:63:56:40:69:70:65:73:6F:66:74:2E:73:6B“

These methods were introduced to support cooperation with IP and MAC addresses of network interfaces.


* D2000 system supports values of objects in the maximum range of 32 bits for signed integer types. Therefore, if the number is bigger, then the maximum value of the 32-bit range will be assigned to it. If the input object of the D2000 system is of Ai type, the system will attempt to convert it to Real.

Permissible types: Di, Ci, Ai, TxI, TiR, TiA

The following table shows the supported conversions of value types:

  • supported conversion

Trap messages receiving and processing


SNMP protocol also allows, except for cyclic value reading, to send messages about important events. These messages are called Traps.
SNMP agent sends the Traps to the configured IP address and port (by default 162), which is configured (simple devices support sending of Traps to one IP address and port, advanced ones send Traps to more addresses).
The Trap IP address parameter must be configured to activate a task that receives the Traps on the Trap port.
Trap receiving is supported in versions V1 and V2C of the SNMP protocol. By default, one device sends Traps using one version of the protocol.
To receive Traps from a particular device, I/O tags with the following text addresses must be configured on the station (however, there is no need to configure all of them):

Text addresses of I/O tags for Traps in the SNMP protocol, version V1:

I/O tag addressData typeDescription
TRAP_ENTERPRISE
OIDOID of the object that generates a Trap (for a particular device, it is constant).
Note: A producer of a device can often be detected from the OID.
TRAP_GENERIC_TRAP
IntegerIdentifier of the Trap class. The following values are defined in RFC 1157 for SNMP, version 1:
  • 0 - coldStart
  • 1 - warmStart
  • 2 - linkDown
  • 3 - linkUp
  • 4 - authenticationFailure
  • 5 - egpNeighborLoss
  • 6 - enterpriseSpecific
TRAP_SPECIFIC_TRAP
IntegerSpecific code of the message.
TRAP_TIMESTAMP
TimeTicks
Time-stamp (according to RFC 1157, it means time (in the hundredth of a second) that passed between the last network reinitialization of the device and the trap generation.

Note: If the I/O tag is Ai - Analog input, its value will be in seconds, i.e., TimeTicks/100.
If the I/O tag is Ci - Integer input, its value will be in hundredths of a second, i.e., in TimeTicks.

TRAP_OID
OIDOID of the object that caused the generation of the Trap or the object to which the Trap relates.
TRAP_VALUE
ArbitraryValue of the object that caused the generation of the Trap or the object to which the Trap relates.

Note 1: Because the value is arbitrary, it is recommended to configure the I/O tag of TxtI - Text input type. Otherwise, some values will not be converted (e.g., to Integer input), and the value of TRAP_VALUE will not be changed.
Note 2: A Trap can contain several pairs (OID, value) as well. In this case, the value of I/O tags with addresses TRAP_OID and TRAP_VALUE will be set for all couples step-by-step. It is possible to configure an event that is initiated when the value of the I/O tag with address TRAP_VALUE is changed, and to save the couples (OID, value) into the database.

TRAP_CONFIRM
BooleanI/O tag that confirms the values processing. Because several pairs of (TRAP_OID, TRAP_VALUE) can exist in one Trap message, the correct processing by an ESL script requires the KOM process to set the next pair after the previous one is processed. Also, the values of other input I/O tags for Trap messages should be set after signalization that the previous values have already been processed.

If the output I/O tag with address TRAP_CONFIRM exists, the KOM process will set the next pair of input I/O tag values after the ESL script writes to the output I/O tag with address TRAP_CONFIRM (the ESL script will perform the writing as one of its last operations). The values of another I/O tags (with addresses TRAP_ENTERPRISE, TRAP_GENERIC_TRAP, TRAP_SPECIFIC_TRAP, TRAP_TIMESTAMP, and TRAP_OID) will be set only when processing the first pair of values (TRAP_OID, TRAP_VALUE). In case of the following pairs, the values of I/O tags will be the same, and they will only be changed during the next Trap message processing.

If the output I/O tag with address TRAP_CONFIRM does not exist, the values of all input I/O tags with addresses TRAP_* will be set immediately after the Trap message occurs. This way, the values can be lost because of the existence of several value pairs in the Trap message or because of a new Trap message arrival, before the user script has processed the previous values.

Text addresses of I/O tags for Traps in the SNMP protocol, version V2C:

I/O tag addressData typeDescription
TRAP_REQUEST_IDIntegerThe increasing Trap number.
TRAP_ERROR_STATUSIntegerError code. The default value is zero (0), but it can acquire one of the following values (see RFC 1448):
  • noError(0)
  • tooBig(1)
  • noSuchName(2)
  • badValue(3)
  • readOnly(4)
  • genErr(5)
  • noAccess(6)
  • wrongType(7)
  • wrongLength(8)
  • wrongEncoding(9)
  • wrongValue(10)
  • noCreation(11)
  • inconsistentValue(12)
  • resourceUnavailable(13)
  • commitFailed(14)
  • undoFailed(15)
  • authorizationError(16)
  • notWritable(17)
  • inconsistentName(18)
TRAP_ERROR_INDEXIntegerExtended error code (often it is 0).
TRAP_UPTIME_OIDOIDOID of object SysUpTime.0. This item should have the value 1.3.6.1.2.1.1.3.0 according to RFC 1448. However, if it's not the case for a specific implementation, the value can be found out using an I/O tag with the address TRAP_UPTIME_OID.
TRAP_UPTIME_VALUETimeTicksValue of object sysUpTime. The Note, mentioned in the description of address TRAP_TIMESTAMP, is also valid for this value.
TRAP_TRAP_OIDOIDOID of object SnmpTrap.0. This item should have the value 1.3.6.1.6.3.1.1.4.1.0 according to  RFC 1448 (i.e., OID of object snmpTrapOID, see RFC 1450). However, if it's not the case for a specific implementation, the value can be found out using an I/O tag with the address TRAP_TRAP_OID.
TRAP_TRAP_OID_VALUE
OIDIdentifier of Trap category, meaning of which corresponds to item TRAP_GENERIC_TRAP in SNMP, version V1, but it is of OID type that allows defining the error codes, specific for particular producers and devices.
The meaning of the standard OIDs, which can the Trap category can obtain (according to RFC 1450), is as follows:
  • 1.3.6.1.6.3.1.1.5.1 - coldStart
  • 1.3.6.1.6.3.1.1.5.2 - warmStart
  • 1.3.6.1.6.3.1.1.5.3 - linkDown
  • 1.3.6.1.6.3.1.1.5.4 - linkUp
  • 1.3.6.1.6.3.1.1.5.5 - authenticationFailure
  • 1.3.6.1.6.3.1.1.5.6 - egpNeighborLoss
  • 1.3.6.1.6.3.1.1.5.7 - enterpriseSpecific
TRAP_OIDOIDThe same meaning as TRAP_OID in SNMP, version V1.
TRAP_VALUEarbitraryThe same meaning as TRAP_VALUE in SNMP, version V1.
TRAP_CONFIRMBooleanThe same meaning as TRAP_CONFIRM in SNMP, version V1.


Note 1: It will be sufficient to configure the input I/O tags with addresses TRAP_OID, TRAP_VALUE and output I/O tag with address TRAP_CONFIRM to confirm the value processing.

Note 2: If the parameter Trap enable has been already configured on the line, the individual task will be activated because of Trap messages processing. This task will receive the messages on the chosen UDP port specified by a link parameter, Trap port (default 162).

If the Trap message processing is configured on the line with address ANY or ALL and on the particular port, it is not possible to configure the Trap message processing on another line and use the same port. It causes a collision. It is, however, possible to configure another parameter, Trap port (e.g., 163), and configure the devices to send Trap messages to this port (e.g., 163).

Note 3: In a redundant system, user must take into consideration that SNMP agents usually support the sending traps to just one IP address (set in advance). Therefore, when redundancy is applied, everything will be ready for receiving traps on the side of D2000 system, but the monitored devices will send traps to the original address. A support of DDNS could be a solution, but only in case the SNMP agent can use DDNS services.

It is the user's responsibility to ensure that the lines will not use the same network interface with the same UDP port. A line with IP address configuration as ANY basically causes blocking (reserving) the UDP port on all network interfaces, which may collide with another TCP-UDP line.  

Browsing and reading the tree of values from the script


The version D2000 7.02.006 and higher supports the dynamic address change of the I/O tag by the SETPTADDR command. This address, together with the I/O tag address GETNEXT_OID, allows browsing and reading the whole tree of values by SNMP request GetNext.

I/O tag addressValue typeDescription
GETNEXT_OID
TxtI - Text inputOID of next object, it is in the response on request GetNext. Only requests that have been generated as a result of the address change of the I/O tag by the SETPTADDR command are taken into consideration, and not the requests that have been generated as a result of cyclic reading of I/O tags.

To read the tree of values, you should configure two input I/O tags of TxtI - Text input type. One of them has the special address GETNEXT_OID, the address of the second I/O tag is set by the SETPTADDR command.
After the address is set, the KOM process will generate the request to read the I/O tag. If the request GetNext is in address (e.g. SETPTADDR M.MySnmpVariable 1.3.6.1.2.1.1 TYPE=3;RQ=1), the OID (sent with reply) will be written into the I/O tag with address GETNEXT_OID (e.g., 1.3.6.1.2.1.1.1.0). After that, the new command containing this address (e.g. SETPTADDR M.MySnmpVariable 1.3.6.1.2.1.1.1.0 TYPE=3;RQ=1) can be sent, and so on.

Example of ESL script that shows browsing and reading the first 100 objects from the tree starting with address 1.3.6.1.2.1.1 and writing the OID addresses and values into the structure _objlist:

 ENTRY query_device_OnClick
   INT _ret
   TIME _t
   TEXT _currOID  ; OID of object prior to object being read
   INT _obj_count ; number of read objects
   RECORD (SD.OID_Value) _objlist ; structure for storing OID+value of read objects

   _obj_count := 0
   _currOID := "1.3.6.1.2.1.1" ; start browsing the tree from successor of this OID
 
   DO_LOOP
     _t := M.SNMP_VariableAddress\TIM ; remember original time
     _ret := COMMAND "SETPTADDR M.SNMP_VariableAddress " + _currOID + " TYPE=3;RQ=1" ON SELF.KOM
     EXIT_LOOP _ret # _ERR_NO_ERROR
 
     DO_LOOP ; wait till the time of variable changes
       EXIT_LOOP _t # M.SNMP_VariableAddress\TIM
       DELAY 1[ms]
     END_LOOP
     
     EXIT_LOOP ! M.SNMP_VariableAddress\VLD ; invalid - error reading value from SNMP
     
     _obj_count := _obj_count + 1
     REDIM _objlist[_obj_count]
     _objlist[_obj_count]^OID := M.SNMP_GetNextOid ; OID of object
     _objlist[_obj_count]^Value := M.SNMP_VariableAddress ; value of object
 
     EXIT_LOOP _obj_count > 100    ; I need only first 100 values
     _currOID := M.SNMP_GetNextOid ; OID of the object which came with GetNext request
   END_LOOP
 END query_device_OnClick
 

Literature


RFC
http://www.ietf.org/rfc.html
http://www.rfc-editor.org/rfcsearch.html

SNMP
http://www.snmplink.org
http://www.simpleweb.org/ietf/rfcs/rfcbymodule.html
http://publib.boulder.ibm.com/infocenter/tpfhelp/current/index.jsp?topic=/com.ibm.ztpf.doc_put.01/gtpc1/gtpc1m0a.htm
http://www.svetsiti.cz/view.asp?rubrika=Tutorialy&temaID=23&clanekID=32
http://www.microsoft.com/technet/archive/winntas/maintain/featusability/networkm.mspx?mfr=true

ASN.1
http://asn1.elibel.tm.fr/en/introduction/index.htm
http://asn1.elibel.tm.fr/en/standards

Changes and modifications


Document revisions


  • 20. 3. 2006 - 1. version (testing version)
  • 31. 7. 2007 - 2. version (SNMP in asynchronous mode)
  • 16. 1. 2009 - GetNext support