MODBUS RTU Quad2000 communication protocol
Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
Supported device types and versions
MODBUS RTU supports the communication with the control systems Quad 2000 of Cooper turbo-compressors.
Communication line configuration
- Communication line category: Serial, SerialOverUDP Device Redundant.
- Transmission parameters according to Quad 2000 (baud rate 300 up to 19200 Baud, 8 data bits, no parity, 1 stop bit).
Communication station configuration
- Communication protocol: MODBUS RTU Quad2000.
- The address is MODBUS address that is set in Quad 2000.
Station protocol parameters
Configuration dialog box - tab "Protocol parameters".
They influence some optional parameters of the protocol. You can define the following parameters:
Table 1
Keyword | Full name | Description | Unit | Default value |
---|---|---|---|---|
RC | Retry Count | The number of request retries when an error in communication occurs. | - | 2 |
RT | Retry Timeout | The delay between request retries if an error in communication occurs. | ms | 100 ms |
WFT | Wait First Timeout | First waiting for a response after sending a request. | ms | 100 ms |
WT | Wait Timeout | Delay between the readings of a response until it is completed. | ms | 100 ms |
MWR | Max Wait Retry | The number of response readings until it is completed. | - | 20 |
String with protocol parameters is written according to this rule:
Key_word=value;Key_word=value; ...
Example:
WT=100;MWR=20;
If a keyword with a valid value has not been found in the initial string, the default value is used according to Table 1.
I/O tag configuration
I/O tags: Ai, Ao, Ci, Co, Di, Do
For the relation between D2000 Value Type and Modbus Data Type, the following table applies:
Modbus Data Type | D2000 Value Type |
---|---|
Coil Status - 0x references | Do |
Input Status - 1x references | Di |
Input Registers - 3x references | Ai, Ci |
Holding Registers - 4x references | Ao, Co |
The address is Modbus register number in the range of 0 to 65535.
For Ai and Ci points, a type of conversion to physical units must be defined. Conversion type RTD, 0-10V, 4-20mA, 1-5V, or none is specified in the documentation (see Literature). You can get more detailed information about the settings of channels directly by browsing the channel configuration on the Quad display. You can also get the limit values "Zero" and "Range" for the conversion of voltage or current inputs.
Literature
- COOPER TURBOCOMPRESSOR - Centrifugal Compressor Quad 2000 - Modbus Communication Description - Release EDR-K-041 Rev.1
Changes and modifications
-
Document revisions
- Ver. 1.0 - October 29, 2002 - Creation of document