There are two object of User variables type, and the script S1 sets their values:
- U.Int - integer value
- U.Text - text representation of the value of U.Int
INT _i
_i := 1
FillNext: U.Int := _i WAIT U.Text := %IToStr(_i) WAIT _i := _i + 1 GOTO FillNext END
The script S2 checks whether the value U.Int is correctly text-represented in the user variable U.Text.
INT _i
TestNext: _i := %StrToI(U.Text) IF _i # U.Int THEN MESSAGE "Not equal" ON WS_BC.HIP ENDIF GOTO TestNext END
This arrangement causes the often occurrence of errors. The operation to assign new values to the variables U.Int a U.Text is interrupted by the script S2 which finds incorrect values in them.
The described problem should be solved using the actions GETACCESS a RELEASEACCESS as follows:
Script S1
INT _i BOOL _ok TEXT _regString = "Access to U.Int" _i := 1 FillNext: _ok := GETACCESS _regString ; provide the access IF _ok THEN U.Int := _i WAIT U.Text := %IToStr(_i) WAIT RELEASEACCESS _regString ; release the access
_i := _i + 1 ENDIF GOTO FillNext END
Script S2
INT _i BOOL _ok TEXT _regString = "Access to U.Int"
TestNext: _ok := GETACCESS _regString ; provide the access IF _ok THEN _i := %StrToI(U.Text) IF _i # U.Int THEN MESSAGE "Not equal" ON WS_BC.HIP ENDIF RELEASEACCESS _regString ; release the access
ELSE
DELAY 100[ms] ENDIF GOTO TestNext END
In such an arrangement, the script S2 accesses to values of the objects U.Int a U.Text only in case its successful text registration by the action GETACCESS. Successful registration means, that the script S1 doesn't modified values of these objects. It is a competitive access of two parallel running events to the same objects.
Related pages:
0 komentárov