Program D2000 CfgSynchrAuto is used for automatic (non-interactive) and complete
synchronization of configuration databases. It is called by process
D2000 Server that is in HS state and receives a synchronization request from another process
D2000 Server attempting to connect to the redundant group.
After being installed program D2000 CfgSynchrAuto is located in the \Bin subdirectory
of the application directory and
it is named cfgsynchroauto.exe or cfgsynchroauto_ora.exe. The first accesses configuration
databases via ODBC interface, the latter via OCI (Oracle Common Interface).
Cfgsynchroauto.exe allows to synchronize configurations stored in Sybase or Oracle database (as for
Oracle, it is necessary to create DSN by means of ODBC driver).
Program cfgsynchroauto_ora.exe only allows to synchronize configurations saved in Oracle database.
Starting D2000 CfgSynchroAuto
Program is run from command line as follows:
Declaration |
cfgsynchroauto.exe srcDSNName dstDSNName userName [dstUserName] [A]
cfgsynchroauto_ora.exe srcTNSName dstTNSName userName [dstUserName] [A]
|
Parameters |
srcDSNName |
DSN of source configuration database. |
dstDSNName |
DSN of destination configuration database. |
srcTNSName |
TNS of source configuration database. |
dstTNSName |
TNS of destination configuration database. |
userName |
User name as a login to source configuration database. |
dstUserName |
User name as a login to destination configuration database.
If not defined differently, the name in the parameter userName is used. This parameter
must be specified when synchronizing a Sybase database with an Oracle database (due
to different way of naming a user of configuration database).
|
A |
If the parameter is used, synchronization automatically carries out an upgrade of database,
if needed. If it is not used, synchronization is terminated with
an error.
Note: Version of configuration database changes as new releases of D2000 system
come out
(not always). Therefore an upgrade is performed by process
D2000 Server while starting.
From version 7.1.X R49 the parameter is ignored and an automatic upgrade of configuration database
is permitted.
|
/NO_OBJLIFE |
If the parameter is used, the object life logs will not be
synchronized.
Note: If the parameter
LogRecsLateSynchro
is set, when starting
D2000 CfgSynchroAuto from D2000 Server process, the parameter /NO_OBJLIFE
will be used when connecting of the SBS Server. I.e. the object life
logs not be synchronized and the synchronization of databases will
take much shorter. |
/ONLY_OBJLIFE |
If the parameter is used, only object life logs will be synchronized. |
|
After finishing its activity, program cfgsynchroauto.exe sets a return code that can be tested. If
the synchronization was successful, its value is 0.