CALCSTATFUNCARR action
Function
Calculation of statistical archive function for all specified item intervals.
Declaration
CALCSTATFUNCARR archIdent, bt_TmA, et_TmA, step, deepTime, statFuncIdent_Int, validPercIdent_Int, paramIdent, locVarColValueIdent_Rec, statusIdent_Int
[,archivInstance_Int]
Parameters
archIdent | in | Reference to one value of historical value or reference to an object, values of which have been archived. Warning: If the parameter is the reference to an object archived several times, there is not specified which one of the historical objects is to be used. |
bt_TmA | in | Identifier of AbsTime type - interval beginning. |
et_TmA | in | Identifier of AbsTime type - interval end. |
step | in | Identifier of Int type - time step [s]. Note: the parameter must be a positive integer. |
deepTime | in | Identifier of Int type - time-depth [s] for calculating the statistics. Note: The parameter must be a positive integer. |
statFunctIdent_Int | in | Identifier of Int type - statistical function type. |
validPercIdent_Int | in | Identifier of Int type - validation criteria. |
paramIdent | in | Identifier of Int or Real types - parameter for some types of functions. |
locVarColValueIdent_Rec | out | Reference to a column of a structured variable of Record type - result values. |
statusIdent_Int | out | Calculation (action) success. |
archivInstance_Int | in | Optional identifier of Int type - identification of archive instance. If the parameter is not defined, the value 0 will replace it. |
Description
The action executes the calculation of the statistical function specified by the statFuncIdent_Int parameter on the values represented by the archIdent historical value for the following time intervals specified by the bt_TmA, et_TmA, step and deepTime parameters:
The statusIdent_Int parameter gets one of the following values:
The validPerctIdent_Int parameter represents the Validation criteria used during the evaluation of the statistical function. It accepts values within 0 .. 100 (the error ERR_RANGE_ERROR occurs if the condition is not met).
For some of the statistical archive functions, the paramIdent parameter must be specified according to the table:
For other statistical archive functions, the paramIdent parameter is not evaluated.
Value of parameter archivInstance_Int defines the instance of the archive which executes the request. If the parameter is not defined (or the value is 0), the active archive instance will execute the request.
- first time interval - <bt_TmA - deepTime; bt_TmA>
- second time interval - <bt_TmA + step - deepTime; bt_TmA + step>
- .....
- n-th time interval - <bt + (N-1)*step - deepTime; bt + (N-1)*step>
The statusIdent_Int parameter gets one of the following values:
- _ERR_TRANS_ABORT
- _ERR_TRANS_ERROR
- _ERR_TRANS_IGNORED
- _ERR_NO_ERROR
The validPerctIdent_Int parameter represents the Validation criteria used during the evaluation of the statistical function. It accepts values within 0 .. 100 (the error ERR_RANGE_ERROR occurs if the condition is not met).
For some of the statistical archive functions, the paramIdent parameter must be specified according to the table:
Statistical function | Parameter description | ||||||||
_STAT_F_INTEGRAL | Integral time units. For individual types, there are also established predefined local variables according to the table:
| ||||||||
_STAT_F_GE_TIME _STAT_F_GT_TIME _STAT_F_LE_TIME _STAT_F_LT_TIME _STAT_F_ADDITION_PARAM _STAT_F_INCREMENT_PARAM _STAT_F_DELTA_PARAM | Compare value |
For other statistical archive functions, the paramIdent parameter is not evaluated.
Value of parameter archivInstance_Int defines the instance of the archive which executes the request. If the parameter is not defined (or the value is 0), the active archive instance will execute the request.
Example
Calculation of the weighted floating average of the values within the range of 2 hours.
TIME _bt TIME _et INT _step INT _deepTime REAL _retCode INT _idx RECORD NOALIAS (SD.Data) _statData _bt := %StrToTime("0:00:00 16-11-2006") _et := %StrToTime("0:00:00 17-11-2006") _step := 3600 ; value for each hour _deepTime := 2*_step ; floating average, time depth of 2 hours CALCSTATFUNCARR H.Col[1], _bt, _et, _step, _deepTime, _STAT_F_WGAVG, 100, 0, _statData^Value, _retCode IF _retCode = _ERR_NO_ERROR THEN ; calculation done, browsing result values FOR _idx=1 TO _statData\DIM DO_LOOP ; _statData[_idx]^Value - value ELSE ; an error occurred ENDIF
Note
Using the CALCSTATFUNC action does not allow evaluating of the FILTER and ECOAVG statistical functions.