Incos PMEL 04 communication protocol
Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
Supported device types and versions
The communication with the impulse power meters Incos/VUVT PM_EL 04 involves obtaining:
- accumulated work for 3 tariffs
- instantaneous power
- quarter-hour power take-off, including the archival data
Communication line configuration
- Communication line category: Serial, SerialOverUDP Device Redundant.
- Communication line parameters - according to the device settings.
Communication station configuration
- Communication protocol: Incos/VUVT PMEL 04.
- A station address is a decimal number - according to the settings of PMEL configuration jumpers.
- A time synchronization of station is required.
Station protocol parameters
Communication station - configuration dialog box -
tab
"Protocol parameters".
They could influence some optional protocol parameters. You can set the
following parameters:
Table 1
Key word | Full name | Meaning | Unit | Default value |
---|---|---|---|---|
RC | Retry Count | Number of call retries when an error in communication occurs. | - | 2 |
RT | Retry Timeout | Delay between the retry call when an error in communication occurs. | ms | 1000 |
WFT | Wait First Timeout | The first timeout for response reading after sending the message. | ms | 500 |
WT | Wait Timeout | Timeout between the response readings until it is completed. | ms | 500 |
MWR | Max Wait Retry | Number of retries of response reading until it is completed. | - | 8 |
SADDR | Source Address | Communication address of source (PC). | 0 up to 254 | 126 |
PMEL04B | PMEL04B | Communication with PMEL04B device. | YES/NO | NO |
TIMEST | Timestamp | There is used PMEL04B with the support of time stamp transmission. | YES/NO | NO |
TMSYNC | Allow Automatic Time Synchro | Real time will be synchronized after the bit EM_TIM is set by a device (only PMEL04B). | YES/NO | YES |
I/O tag configuration
- I/O tags: Ai, Di, TiA, TiR.
- I/O tag address is a decimal number in the range 0 up to 255.
Table 2: I/O tag addresses distribution:
Electro meter | Instantaneous power (Ai) | Accumulation work tariff 1 (Ai) | Accumulation work tariff 2 (Ai) | Accumulation work tariff 3 (Ai) | Quarter-hour power take-off (Ai) | Time difference between curr. and prev. state (TiR) |
---|---|---|---|---|---|---|
1 | 0 | 16 | 17 | 18 | 64 | 200 |
2 | 1 | 19 | 20 | 21 | 65 | 201 |
3 | 2 | 22 | 23 | 24 | 66 | 202 |
4 | 3 | 25 | 26 | 27 | 67 | 203 |
5 | 4 | 28 | 29 | 30 | 68 | 204 |
6 | 5 | 31 | 32 | 33 | 69 | 205 |
7 | 6 | 34 | 35 | 36 | 70 | 206 |
8 | 7 | 37 | 38 | 39 | 71 | 207 |
9 | 8 | 40 | 41 | 42 | 72 | 208 |
10 | 9 | 43 | 44 | 45 | 73 | 209 |
11 | 10 | 46 | 47 | 48 | 74 | 210 |
12 | 11 | 49 | 50 | 51 | 75 | 211 |
13 | 12 | 52 | 53 | 54 | 76 | 212 |
14 | 13 | 55 | 56 | 57 | 77 | 213 |
15 | 14 | 58 | 59 | 60 | 78 | 214 |
16 | 15 | 61 | 62 | 63 | 79 | 215 |
Table 3: Di values, status bits (only PMEL04A):
Address | Meaning |
---|---|
0 | EPROM error. |
1 | RAM error. |
5 | Program restart on a process module. |
6 | Exceeding the time difference. |
7 | Acknowledgement of time settings. |
Di values, digital inputs (only PMEL04B), addresses 0 up to 15.
Table 4: Di values, status bits (only PMEL04B):
Address | Meaning |
---|---|
100 | RES_CNT |
107 | EM_TIM |
108 | EM_ROM |
109 | EM_RAM |
110 | TDIFOVR |
Literature
-
Changes and modifications
-
Document revisions
- Ver. 1.0 - February 18, 2000 - Creation of document
- Ver. 1.1 - March 13, 2008 - Updating